CQ SERIES
CQ 1 - AC power sequencer shall be mountable in a wall (or ceiling or enclosure) using standard trade hardware in a two or three gang enclosure. It shall feature one fifteen amp rated duplex receptacle which will turn on and off via remote control when connected to other Juice Goose CQ Series power control devices (or a remote latching contact closure). Connection to other remote control devices shall be by way of RJ45 cabling. This unit shall have the ability to integrate in a "daisy chain" manner with other power units in sequence before and/or after it. Actual current switching shall be by way of a mechanical relay. It shall have a single LED on the faceplate to indicate power to the control board and proper operation of the control circuitry.
CQ 50 - AC power sequencer shall be fifteen amp rated device with a detachable power cord to plug into available utility power. It shall be mountable on a flat surface using the product’s mounting flanges and shall not require a rack for installation. It shall feature one unswitched AC receptacle and two switched receptacles which turn on and off in one sequence event via remote control when connected to other Juice Goose CQ Series power control devices (or a remote latching contact closure). Connection to other remote control devices shall be by way of RJ45 cabling. This unit shall have the ability to integrate in a "daisy chain" manner with other power units in sequence before and/or after it. Actual current switching shall be by way of a mechanical relay. It shall have two LEDs on the enclosure to indicate status of the power Pod proper operation of the control Processor.
CQ 1515 - Rack mounted electric power sequencer shall be the Juice Goose CQ 1515. It shall feature one unswitched AC receptacle plus three fifteen amp duplex receptacles which will turn on and off in three sequence steps on a single 15 amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of mechanical relays of a minimum 30 amp rating. It shall also have LED indications that each sequence event is completed. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors. Additional features shall include AC line filtration and power surge protection across the hot, neutral and ground leads.
CQ 1520 - Rack mounted electric power sequencer shall be the Juice Goose CQ 1520. It shall feature one unswitched AC receptacle plus three twenty amp duplex receptacles which will turn on and off in three sequence steps on a single 20 amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of mechanical relays of a minimum 30 amp rating. It shall also have LED indications that each sequence event is completed. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors. Additional features shall include AC line filtration and power surge protection across the hot, neutral and ground leads.
CQ 15__-RX - Rack mounted electric power sequencer shall be the Juice Goose CQ 15__-RX (either CQ1520-RX or CQ1515-RX) which shall feature AC power sequencing in addition to a maximum 1/2 volt surge let through on the ground and a maximum 10 volt surge let through between line and neutral. It shall also feature one unswitched AC receptacle plus three duplex receptacles which will turn on and off in three sequence steps on a single __ (15 or 20) amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of mechanical relays of a minimum 30 amp rating. It shall also have LED indications that each sequence event is completed. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors. Additional features shall include AC line filtration and power surge protection across the hot, neutral and ground leads.
CQ 2200 - Electric power sequencer shall be the Juice Goose CQ 2200. It shall feature two twenty amp duplex receptacle which will turn on and off in two sequence steps on a single 20 amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of two mechanical relays of a minimum 30 amp rating. It shall also have LED indications that each sequence event is completed. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors.
CQ 3000 - Electric power sequencer shall be the Juice Goose CQ 3000. It shall feature one thirty amp twist lock receptacle (NEMA L5-30R) which will turn on and off on a single 30 amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of one mechanical relay with two, parallel 30 amp rated circuit paths. The relay shall have silver cadmium contacts. The sequencer shall also have LED indications that the sequence event is completed. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors.
CQ PD1-4 - Rack mounted electric power sequencer shall be the Juice Goose CQ PD1-4. It shall feature four twenty amp duplex receptacles which will turn on and off in four sequence steps, each on an individual 20 amp circuit. Power input connections shall be by a four foot wire harness which shall exit from the top of the unit. The sequencer shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. This device shall also be capable of triggering other similar power activation devices. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of mechanical relays of a minimum 30 amp rating. Interconnection of this unit with other sequencers or trigger devices shall be by way of RJ45 cables and connectors.
RC5 - Remote control and monitoring of the power sequencing device shall be by way of Juice Goose model RC5. This device shall be mountable in a rack or on a wall or panel and shall provide a method for sequencing the AC power system up, sequencing it down or pausing it in either process. It shall require no secondary power supply. In a typical power sequencing system the remote control shall be connected only to a first power sequencing device and shall be the initial step in activating the system. Selection of a particular remote control model shall be determined by specific security and convenience requirements. In cases where access to the remote control location is limited to only authorized personnel, the model may be one with a rotary switch. In cases where the remote control location is available to unauthorized individuals a key switch remote control device shall be used. The remote control device shall feature lighted indicators for system operation and system status.
RC5-KPS - Sequencing operation shall require the user to enter a four digit code using the three push buttons on the remote control. Entering that code will sequence the system up if it is down or sequence it down if it is up. The code shall be changeable using a factory preset administration code.
SQ 1500 - Rack mounted electric power sequencer shall be the Juice Goose SQ 1500. It shall feature one unswitched AC receptacle plus three duplex receptacles which will turn on and off in three sequence steps on a single 15 amp circuit. It shall not require a remote control device to operate but shall be capable of being activated by a remote, latching contact closure. The sequencer shall have an override switch to turn on the unit in the event of failure of the main control circuit. Actual current switching shall be by way of mechanical relays of a minimum 30 amp rating. It shall also have LED indications that each sequence event is completed. Additional features shall include AC line filtration and power surge protection across the hot, neutral and ground leads.